1. Home
  2. Products
  3. 90 kVA Bidirectional Four-Wire DC/AC Converter

Overview

The Silicon Carbide (SiC) topology delivers 98.5 % peak efficiency over a broad operating range and yields a more compact package through higher power density. The system is fully sealed and liquid cooled, ready to deploy in harsh environments, including off-highway applications.

The GN01 inverter operates on-grid, off-grid, or as part of a smart microgrid. Its active neutral supports load imbalances up to 100 % per phase, ensuring stable performance even under highly uneven load distributions. The unit is fully user-configurable for any standard voltage up to 480 VAC and frequencies up to 400 Hz, making it compatible to a wide range of power grids across industries globally. It functions to stabilize voltage and frequency, balancing demand peaks, and delivering cleaner, more reliable power to the grid.

AC Droop control lets the user set target voltage and frequency, then overlay bidirectional active and reactive power control — useful for storage regulation, seamless AC synchronization, AC hot swaps, and generator hybridization. Droop parameters are exposed for real-time tuning by integrators, rather than locked behind firmware. Each unit takes CAN control locally, but coordination across units happen on the AC waveform itself. Voltage and frequency carry the signal, so any number of units can run in parallel on a shared AC grid without an additional communications layer between them.

When connected to a grid, GN01 can idle alongside the mains while the battery handles other duties, such as peak shaving, frequency regulation, or standing by. If an upstream breaker opens, including during islanding events, the inverter assumes the load with no transfer interruption. This delivers reliable ride-through performance equivalent to a uninterruptible power supply (UPS) as a native function of the grid-forming control, without a dedicated UPS in the system.

Characteristics

  • Power up to megawatt levels through paralleling

  • Full bidirectional operation for charging through the same converters

  • Support for all common grid standards up to 480 V, single-, split- and three-phase inverters, 50 - 400 Hz

Applications

  • Portable battery gensets (90 kW up to megawatt levels)

  • Off-grid and on-grid operation

  • Balancing microgrids

  • Microgrid capable BESS

  • Integration with other power sources such as solar and diesel generation

  • Portable DC fast charging, by integrating ADM-PC-DC01

Technical Data

Electrical

Rated AC voltage (L-L)

208 - 480 Vrms, reduced power below 380 Vrms

Rated AC frequency

50 / 60 / 400 Hz

Maximum AC current

±135 Arms, per phase

Maximum neutral current

±135 Arms

Power factor (PF)

≥0.99

Total Harmonic Distortion THDI

≤5 %, for loads above 20 %

Power Control

±0.9 inductive-capacitive

Wiring

L1, L2, L3, N

Startup

Internal soft start

Inrush current

Less than nominal current

Phase to PE separation

Basic isolation

Protection

Overvoltage, undervoltage, overcurrent, overtemperature

Fusing

Yes, UL/IEC rated

Overvoltage category

OVC2

Grid generation

Forming, following, microgrid

Connectors AC

4x RADSOK Size 8 mm Amphenol SurLock Plus (SLP-HIR-B)

DC Voltage range

360 - 950 V (min DC voltage depends on the mains voltage)

DC Current

±160 A bidirectional limited by power envelope

Max power (400 V/50 Hz)

93 kW

Current measurement accuracy

±1 % of full-scale

Voltage measurement accuracy

±1 % of full-scale

Primary-Secondary separation

Non-isolated

Fusing

Yes, on positive line, UL/IEC rated

AC Relays (Grid Side)

Yes

Connectors DC

2x port A, RADSOK Size 8 mm Amphenol SurLock Plus (SLP-HIR-B)

Low voltage and communication

Communication interface

CAN 2.0B

External control power supply voltage

24 V nominal (20-28 V)

Control power consumption

50 W

Standby power consumption

5 W

Isolation concept

CAN and 24 V isolated from PE CAN bus isolated from 24 V Basic isolation, reinforced towards HV

Connectors

2x for CAN, 1x for power

Paralleling of converters

Up to 120 units in parallel

Mechanical

Dimensions

700 x 400 x 165 mm

Weight

43 kg

Cooling

50/50 Water Ethylene Glycol Mix

Noise

Small internal fan

Mounting

4U rack, or custom brackets

Environment

Operating temperature range

-40 to 70 °C, derating applies

Ingress protection code

IP67

Allowed pollution degree

3 external environment

Altitude

3000 m

Shock

Pending

Vibrations

Designed for harsh environments

Standards

Designed to following standards

IEC 61851-1, 61851-23 ED2, IEC 62477-1, UL2202, UL1741

Grid code support

EN50549-1, IEEE 1547, VDE-AR-N 4100, UK G99, AS 4777.2

Electromagnetics compatibility

EMC class B possible with an external filter

General

Support

ADVANTICS Helpdesk included

Design and Manufacturing

EU

Please note that the technical data presented on the website is for reference only and may be subject to change without prior notice.

Take a closer look